JalaRakshak AIby quaStrat

Methodology & Reset

jalarakshak-engine-ts-1.0 (port of reference_engine.py) · demo-seed-2026-10-12

Equations

  • ΔP = discharge_bar − suction_bar
  • hydraulic_kW = flow_m³h × ΔP / 36
  • η_w2w = hydraulic_kW / electric_kW
  • Reject reading if flow < 50 m³/h, ΔP < 0.5 bar, kW < 2, field missing, or η outside 0..1.
  • Baseline = median η of first 7 days; recent = median η of last 7 days; ≥5 valid days each.
  • deterioration % = max(0, (baseline − recent)/baseline × 100)
  • Pump index = 10 + min(30, 1.5 × deterioration) + vibration (+18 watch / +32 high) + bearing temp (+8 / +18) + repeat low-flow (+10) + open issue (+8), capped at 100.
  • Mitigation points = index × criticality / 5 × mitigation fraction; inspections = 0.
  • Maximise Σ(mitigation + λ × information) s.t. budget, crew hours, outage, one action per asset, verified evidence gates. Exact exhaustive enumeration.

Assumptions & warnings

  • All assets, readings, costs, dates and thresholds are fictitious. No BWSSB, SCADA or GIS connection.
  • The condition index is an explainable demonstration index, not a probability of failure.
  • Thresholds are illustrative, not industrial-standard limits or BWSSB-approved criteria.
  • Inspections improve information only; they do not physically reduce failure risk.
  • Composite improvement is not proven failure prevention.
  • The ₹1,30,000 scenario budget is unrelated to the Government First ₹25 lakh pilot budget.
  • No equipment actuation, SCADA write or work scheduling occurs.

Numerical self-test: 14/14 passed

TestExpectedComputedResult
P-101 assessment12.1 / conf 0.9512.1 / conf 0.95PASS
P-102 assessment58 / conf 0.9558 / conf 0.95PASS
P-103 assessment44 / conf 0.9544 / conf 0.95PASS
P-104 assessmentnull / conf 0.1null / conf 0.1PASS
V-201 assessment78 / conf 0.978 / conf 0.9PASS
V-202 assessment12 / conf 0.6212 / conf 0.62PASS
VFD-301 assessment38 / conf 0.8538 / conf 0.85PASS
MCC-401 assessment10 / conf 0.8510 / conf 0.85PASS
Base optimisedA-01,A-06,A-08,A-10,A-11 · ₹98500 · 18h · 90m · 107.940A-01,A-06,A-08,A-10,A-11 · ₹98500 · 18h · 90m · 107.940PASS
Base risk-first greedyA-06,A-01,A-04,A-09 · ₹102500 · 17h · 90m · 98.414A-06,A-01,A-04,A-09 · ₹102500 · 17h · 90m · 98.414PASS
After P-102 strainer_blockedA-03,A-06,A-09,A-11 · ₹103500 · 18h · 105m · 109.524A-03,A-06,A-09,A-11 · ₹103500 · 18h · 105m · 109.524PASS
Restricted budgetA-06,A-08,A-11 · ₹77000 · 13h · 90m · 83.640A-06,A-08,A-11 · ₹77000 · 13h · 90m · 83.640PASS
A-02 stays gated after strainer findingblockedblockedPASS
Inspections have zero physical mitigation00PASS

Reset demo