P-102 · Pump Train 2
Pump train · duty · criticality 5/5 · commissioned 2014 · source GIS-P-102
Condition index vs confidence
Index 58.0
Condition index (0–100)
58
Evidence confidence
0.95
Index is an explainable demonstration score, not a probability of failure.
Plain-English explanation
Median wire-to-water efficiency fell from 0.7121 (first week, 7 valid days) to 0.5674 (last week, 7 valid days), a 20.32% deterioration. Recent median vibration is 4.07 mm/s and bearing temperature 77.75 °C. The cause is not established by these data.
- Wire-to-water efficiency decreased 20.3% versus first-week asset baseline
- Recent median bearing temperature exceeds synthetic watch threshold
- Repeat low-flow work-order history
- Inspection overdue by 22 days; this affects inspection priority, not proof of physical failure
baseline wire to water efficiency: 0.7121recent wire to water efficiency: 0.5674efficiency drop pct: 20.32recent median vibration mm s: 4.07recent median bearing temp c: 77.75valid baseline days: 7valid recent days: 7
Wire-to-water efficiency (valid days)
Vibration mm/s
Bearing temperature °C
Raw readings (28)
Swipe sideways to see all columns.
Baseline window: before 2026-09-21. Recent window: from 2026-10-05. Source: SYNTHETIC historian daily summary.
| Date | Flow m³/h | Suct. bar | Disch. bar | ΔP bar | kW in | Hydr. kW | Eff. | Vib. | Brg °C | Status |
|---|---|---|---|---|---|---|---|---|---|---|
| 2026-09-14 | 216.00 | 1.03 | 5.54 | 4.507 | 37.90 | 27.04 | 0.7135 | 2.45 | 69.00 | valid |
| 2026-09-15 | 217.24 | 1.03 | 5.53 | 4.504 | 38.02 | 27.18 | 0.7149 | 2.50 | 69.43 | valid |
| 2026-09-16 | 217.95 | 1.03 | 5.53 | 4.495 | 38.09 | 27.21 | 0.7145 | 2.53 | 69.68 | valid |
| 2026-09-17 | 217.81 | 1.03 | 5.51 | 4.482 | 38.08 | 27.12 | 0.7121 | 2.52 | 69.63 | valid |
| 2026-09-18 | 216.89 | 1.03 | 5.50 | 4.469 | 37.99 | 26.92 | 0.7087 | 2.49 | 69.31 | valid |
| 2026-09-19 | 215.59 | 1.03 | 5.49 | 4.458 | 37.86 | 26.70 | 0.7052 | 2.43 | 68.86 | valid |
| 2026-09-20 | 214.46 | 1.03 | 5.48 | 4.453 | 37.75 | 26.53 | 0.7027 | 2.39 | 68.46 | valid |
| 2026-09-21 | 214.00 | 1.03 | 5.49 | 4.455 | 37.70 | 26.48 | 0.7025 | 2.37 | 68.30 | valid |
| 2026-09-22 | 214.40 | 1.03 | 5.49 | 4.462 | 37.74 | 26.57 | 0.7041 | 2.39 | 68.44 | valid |
| 2026-09-23 | 215.50 | 1.03 | 5.50 | 4.474 | 37.85 | 26.78 | 0.7076 | 2.43 | 68.82 | valid |
| 2026-09-24 | 215.51 | 1.03 | 5.51 | 4.476 | 38.22 | 26.80 | 0.7011 | 2.59 | 69.88 | valid |
| 2026-09-25 | 215.17 | 1.03 | 5.50 | 4.475 | 38.56 | 26.75 | 0.6936 | 2.74 | 70.82 | valid |
| 2026-09-26 | 214.07 | 1.03 | 5.50 | 4.470 | 38.82 | 26.58 | 0.6847 | 2.86 | 71.49 | valid |
| 2026-09-27 | 212.11 | 1.03 | 5.49 | 4.458 | 38.99 | 26.27 | 0.6737 | 2.94 | 71.86 | valid |
| 2026-09-28 | 209.59 | 1.03 | 5.47 | 4.440 | 39.11 | 25.85 | 0.6609 | 3.00 | 72.03 | valid |
| 2026-09-29 | 207.03 | 1.03 | 5.45 | 4.417 | 39.22 | 25.40 | 0.6477 | 3.06 | 72.19 | valid |
| 2026-09-30 | 204.98 | 1.03 | 5.42 | 4.392 | 39.39 | 25.01 | 0.6349 | 3.14 | 72.53 | valid |
| 2026-10-01 | 203.75 | 1.03 | 5.40 | 4.368 | 39.64 | 24.72 | 0.6237 | 3.26 | 73.15 | valid |
| 2026-10-02 | 203.33 | 1.03 | 5.38 | 4.347 | 39.96 | 24.55 | 0.6144 | 3.40 | 74.06 | valid |
| 2026-10-03 | 203.33 | 1.03 | 5.36 | 4.333 | 40.33 | 24.47 | 0.6068 | 3.56 | 75.11 | valid |
| 2026-10-04 | 203.18 | 1.03 | 5.36 | 4.325 | 40.69 | 24.41 | 0.5999 | 3.72 | 76.12 | valid |
| 2026-10-05 | 202.40 | 1.03 | 5.35 | 4.323 | 40.98 | 24.30 | 0.5931 | 3.85 | 76.90 | valid |
| 2026-10-06 | 200.75 | 1.03 | 5.35 | 4.324 | 41.18 | 24.11 | 0.5855 | 3.95 | 77.38 | valid |
| 2026-10-07 | 198.39 | 1.03 | 5.36 | 4.325 | 41.32 | 23.83 | 0.5768 | 4.01 | 77.61 | valid |
| 2026-10-08 | 195.77 | 1.03 | 5.35 | 4.323 | 41.43 | 23.51 | 0.5674 | 4.07 | 77.75 | valid |
| 2026-10-09 | 193.47 | 1.03 | 5.34 | 4.315 | 41.57 | 23.19 | 0.5578 | 4.14 | 78.00 | valid |
| 2026-10-10 | 191.92 | 1.03 | 5.33 | 4.301 | 41.78 | 22.93 | 0.5488 | 4.24 | 78.51 | valid |
| 2026-10-11 | 191.22 | 1.03 | 5.31 | 4.280 | 42.08 | 22.73 | 0.5403 | 4.37 | 79.32 | valid |
Inspection evidence
No inspection records.
Maintenance history
- WO-0002 · 2026-08-22
reactive low flow: closed — Low-flow event; root cause not confirmed - WO-0003 · 2026-09-08
reactive low flow: closed — Repeat reduced output; follow-up suggested